If you're a property owner or manager dealing with backflow prevention for the first time, you've probably run into two acronyms: RPZ and DCVA. Maybe your water provider told you that you need one or the other. Maybe a plumber recommended an RPZ but you're not sure why it costs more than a double check. Or maybe you're just trying to understand what's already installed on your property.

At 1-A Services, we install, test, repair, and replace both types every single day. Let's break down the differences in plain English so you can make an informed decision โ€” or at least understand what your water provider is asking for.

What Is a DCVA (Double Check Valve Assembly)?

A Double Check Valve Assembly โ€” usually just called a "double check" โ€” is a backflow preventer that uses two independently operating check valves in series. Each check valve is spring-loaded and designed to close when water tries to flow backward. The idea is simple: if one check valve fails, the other one is still there as a backup.

Key characteristics of a DCVA:

  • Two check valves in series, each with its own spring and seat
  • Four test cocks that allow a certified tester to check each valve independently
  • No relief valve โ€” if both checks fail, there's no mechanism to dump water and alert you to the failure
  • Lower pressure loss than an RPZ, which means less impact on your water pressure
  • Can be installed in a vault below grade โ€” this is a significant advantage in many situations
  • Generally less expensive to purchase and install than an RPZ of the same size

DCVAs are approved for low-to-moderate hazard connections. That means situations where a backflow event would be unpleasant or a nuisance, but not a serious health threat. Common applications include domestic water lines to commercial buildings, some irrigation systems (without chemical injection), and fire sprinkler lines in certain configurations.

What Is an RPZ (Reduced Pressure Zone Assembly)?

A Reduced Pressure Zone assembly โ€” commonly called an RPZ or RP โ€” is a more robust backflow preventer. Like a DCVA, it has two check valves. But it also has a relief valve between them that opens and dumps water if the check valves fail. This is the critical difference.

Key characteristics of an RPZ:

  • Two check valves in series, just like a DCVA
  • A hydraulically operated relief valve in the zone between the two checks
  • Four test cocks for annual testing
  • Fail-safe design: If either check valve fails, the relief valve opens and discharges water to the atmosphere. This prevents backflow even in a worst-case scenario, but it also means the RPZ will dump water โ€” sometimes a lot of water โ€” when there's a problem.
  • Must be installed above grade in most jurisdictions because the relief valve needs an air gap to discharge. You cannot install an RPZ in a below-grade vault in most Texas municipalities.
  • Higher pressure loss than a DCVA due to the additional relief valve
  • More expensive to purchase, install, and maintain

RPZs are required for high-hazard connections โ€” situations where a backflow event could pose a serious health risk. This includes connections to fire sprinkler systems with chemical additives, irrigation systems with fertilizer or pesticide injection, boiler systems, medical facilities, car washes, and any connection where toxic or hazardous substances could enter the water supply.

How Your Water Provider Decides Which One You Need

Your water provider's cross-connection control department determines the required level of protection based on the degree of hazard at your property. They evaluate what's connected to your plumbing and how much risk those connections pose to the public water supply.

Here's a simplified breakdown:

  • DCVA is typically acceptable for: Standard commercial domestic water service, fire sprinkler systems with no chemical additives, irrigation systems without chemical injection, and other low-to-moderate hazard connections.
  • RPZ is typically required for: Fire sprinkler systems with antifreeze or chemical additives, irrigation systems with fertilizer/pesticide injection, boiler systems, cooling towers, medical and dental facilities, restaurants and food processing, car washes, and any connection classified as high hazard.

Important: your water provider has the final say. Even if you think a DCVA should be sufficient, if they require an RPZ, that's what you need to install. Don't fight it โ€” the requirements are based on protecting public health.

Installation Considerations

The choice between RPZ and DCVA affects more than just the cost of the device. Here are practical considerations:

Location

RPZs must be installed above grade with adequate drainage for the relief valve discharge. This means they're visible, exposed to weather, and need freeze protection in winter. DCVAs can go in below-grade vaults, which keeps them out of sight and somewhat protected from the elements โ€” but vaults can flood and make access for testing more difficult.

Drainage

An RPZ relief valve can discharge a significant volume of water. You need a plan for where that water goes. Some properties install RPZs over landscape areas or connect the discharge to a storm drain (where permitted). If you don't plan for drainage, you'll end up with flooding around the assembly.

Freeze Protection

In North Texas, we get freezing temperatures every winter. Above-grade RPZs are vulnerable to freeze damage, which can crack the body and destroy internal components. Insulated enclosures or heat tape are common solutions. DCVAs in below-grade vaults are somewhat protected from freezing, but vaults can still freeze in extended cold snaps.

Maintenance Costs

RPZs generally cost more to maintain than DCVAs. The relief valve adds another component that can fail and need repair. RPZ repair kits are more expensive, and the assemblies require more frequent attention. Budget accordingly.

What About PVBs and SVBs?

You might also hear about Pressure Vacuum Breakers (PVBs) and Spill-Resistant Vacuum Breakers (SVBs). These are simpler, less expensive devices used primarily on irrigation systems. They're not approved for all applications โ€” they can't handle continuous pressure, for example โ€” but they're a good option where they're permitted. Your water provider will tell you if a PVB is acceptable for your connection.

Our Recommendation

At 1-A Services, we don't have a preference between RPZ and DCVA โ€” we install, test, and repair both every day. The right choice depends entirely on your property's hazard classification and your water provider's requirements. What we do recommend is working with a company that understands both types, can advise you on installation best practices, and will be there for annual testing and any repairs down the road.

If you're not sure which type of backflow preventer your property needs, or if you've received a notice from your water provider and aren't sure what it means, give us a call. We'll help you figure it out โ€” no charge for the conversation. That's just how we do things.

Need Service?